Cable & conductor sizing

Cable Sizing Calculator

Size a cable by ampacity, voltage drop and short-circuit withstand — to IEC 60364-5-52 or NEC Table 310.16.

For low-voltage installations up to 1000 V AC. Not for medium- or high-voltage cable (which uses IEC 60287).

Inputs

A

Full-load / design current of the circuit.

V

Line-to-line for 3-phase; supply voltage for 1-phase.

IEC 60364-5-52 reference installation method.

m

Cable route length in one direction.

%

Typical: 3% final circuits, 5% total.

°C

Number of grouped circuits (1 = a single circuit).

Short-circuit withstand (optional)
kA

Leave blank to skip this check.

s

Disconnection time of the protective device.

Results update automatically as you enter values.

Result

Enter your circuit details — the recommended conductor size appears here.

How this size is chosen

A conductor must pass three checks, and the size is set by whichever is strictest:

1. Ampacity — the cable's current-carrying capacity, after derating for ambient temperature and grouping, must be at least the design current. 2. Voltage drop — the drop over the run must stay under your limit (often 3–5%). Long runs are usually decided here, not by ampacity. 3. Short-circuit withstand — during a fault, the conductor must not overheat before the protection clears (adiabatic check, IEC 60364-5-54).

The course walks through why each check exists and how to defend the final size in a design review.